Public Notice : Notice issued under section 64(2) of the Electricity Act 2003
2009-10


Download :Tariff Petition
'PDF Format'
Download Acrobat Reader

 

3. Generation Performance and Projection

3.1 Generation Performance

The Petitioner has existing generation facility of 420 MW (2x210 MW) coal based thermal power plant at Bokaro and is also envisaging a plan for extension of another three units (Stage II) of 210 MW each.

Table 1 provides the performance of the generating units for the past four years and the projected generating units for 2009-10.

Table 7: Generation Performance  Actual (MU)

Year

Generation (MUs)

Total

Station PLF (%)

Auxiliary Consumption

(%)

Unit –I

Unit-II

2005-06

1240

289

1529

41.56

14.23

2006-07

1412

1303

2715

73.80

12.04

2007-08

226

1569

1795

48.86

9.95

2008-09

826

1397

2223

60.43

8.37

2009-10

1500

990

2490

67.68

9.00

With the overhauling of unit I, petitioner expects the generation performance to further improve for FY 10.Also, unit II would be under capital maintenance for a period of three months, thereby generating only 990 MU.


3.2 Plant Load Factor (PLF)

A PLF of 67.68% is being projected for the plant in FY10. This increase is projected largely due to the availability of the first unit and better performance of unit II. As Unit II is expected to be available only for 9 months, the projected PLF is still lower than the normative value.

Table 8: Projected Generation Performance for FY10

Year

Generation (MUs)

PLF (%)

2007-08

1795

48.86%

2008-09

2223

60.43%

2009-10

2490

67.68%

3.3 Auxiliary Consumption

The auxiliary consumption is specific to a particular power station and depends on its configuration, age and related technical parameters. Auxiliary power is required for different equipments like feed pumps, cooling water pumps, air fans, coal grinding mills, ash handling equipments, common auxiliaries etc. of the generating station. The auxiliary consumption was 8.37% in FY 2008-09. Petitioner projects its auxiliary consumption at 9% for FY 10

Table 9: Auxiliary Consumption for FY’10

Year

Auxiliary Consumption (%)

2008-09

8.37

2009-10

9.00

3.4 Heat Rate

The actual heat rate for the generating plant has been 3075 kCal/kWh for the FY 2008-09,  In the year 2009-10, petitioner proposes a heat rate of 3100 Kcal/kWh and hence would maintain the last year performance.

Table 10: Projected Heat Rate for FY’10

Year

Heat Rate (kCal/kWh)

2009-10

3100

3.5 Specific Coal Consumption

The Petitioner sources D grade coal from the collieries of Central Coal Fields Limited with calorific value of about 4200 kCal/kg.

Table 11: Specific Coal Consumption

Year

 

Specific Coal Consumption

(kg/kWh)

2000-01

0.705

2001-02

0.706

2002-03

0.695

2003-04

0.680

2004-05

0.685

2005-06

0.688

2006-07

0.656

2007-08

0.689

2008-09

0.715

2009-10

0.720

The Hon’able Commission has followed a trend of fixing a very stiff target for specific coal consumption. CEA reports on performance of thermal power plants have always brought out the fact that eastern region plants have a higher average values. The petitioner has always been achieving better figures in the region.  Petitioner thereby requests the Honorable Commission to consider the specific coal consumption of 0.720 Petitioner in its generation plant for FY 10

Table 12: Specific Coal Consumption for FY’10

Year

Specific Coal Consumption (kg/kWh)

2009-10

0.720

3.6 Secondary Fuel Consumption

Due to the large number of outages experienced by the station due to transmission line trippings etc., the Petitioner has not been able to achieve the norm of 2 ml/kWh fixed by the Honourable Commission for specific oil consumption. The Petitioner observed a specific oil consumption of 2.78 ml/kWh during FY 2008-09 The following Table 7 below provides the trend in specific oil consumption over the last 7 years.

Table 13: Specific Oil Consumption

Year

Specific Oil Consumption

(ml/kWh)

2004-05

2.33

2005-06

3.39

2006-07

2.31

2007-08

1.95

2008-09

2.78

Petitioner is planning to reduce its oil consumption and improve the specific oil consumption figure. Petitioner projects a specific oil consumption of 2.5 ml/kWh

Table 14: Projected Specific Oil Consumption for FY’10

Year

Specific  oil consumption (ml/kWh)

2009-10

2.50

3.7 Summary

The Petitioner projects the following for the FY 2008-09:

Table 15: Projected Generation Parameters for FY’07

Year

Generation (MU)

PLF (%)

Auxiliary Consumption (%)

Heat Rate (kCal/kWh)

Specific Coal Consumption (kg/kWh)

Specific Oil Consumption (ml/kWh)

2000-10

2500

67.68%

9

3100

0.720

2.50

 