Table 8: Projected Generation
Performance for FY10
|
Year |
Generation (MUs) |
PLF (%) |
|
2007-08 |
1795 |
48.86% |
|
2008-09 |
2223 |
60.43% |
|
2009-10 |
2490 |
67.68% |
|
The auxiliary consumption is specific to a
particular power station and depends on its configuration,
age and related technical parameters. Auxiliary power is
required for different equipments like feed pumps, cooling
water pumps, air fans, coal grinding mills, ash handling
equipments, common auxiliaries etc. of the generating
station. The auxiliary consumption was 8.37% in FY
2008-09. Petitioner projects its auxiliary consumption at
9% for FY 10
Table 9: Auxiliary Consumption for
FY’10
|
Year |
Auxiliary Consumption (%) |
|
2008-09 |
8.37 |
|
2009-10 |
9.00 |
|
The actual heat rate for the generating plant
has been 3075 kCal/kWh for the FY 2008-09, In the year
2009-10, petitioner proposes a heat rate of 3100 Kcal/kWh
and hence would maintain the last year performance.
Table 10: Projected Heat Rate for FY’10
|
Year |
Heat Rate (kCal/kWh) |
|
2009-10 |
3100 |
|
The Petitioner sources D grade coal from the
collieries of Central Coal Fields Limited with calorific
value of about 4200 kCal/kg.
Table 11: Specific Coal Consumption
|
Year |
|
|
Specific Coal
Consumption
(kg/kWh) |
|
2000-01 |
0.705 |
|
2001-02 |
0.706 |
|
2002-03 |
0.695 |
|
2003-04 |
0.680 |
|
2004-05 |
0.685 |
|
2005-06 |
0.688 |
|
2006-07 |
0.656 |
|
2007-08 |
0.689 |
|
2008-09 |
0.715
|
|
2009-10 |
0.720 |
|
The Hon’able Commission has followed a trend
of fixing a very stiff target for specific coal
consumption. CEA reports on performance of thermal power
plants have always brought out the fact that eastern
region plants have a higher average values. The petitioner
has always been achieving better figures in the region.
Petitioner thereby requests the Honorable Commission to
consider the specific coal consumption of 0.720 Petitioner
in its generation plant for FY 10
Table 12: Specific Coal Consumption
for FY’10
|
Year |
Specific Coal Consumption (kg/kWh) |
|
2009-10 |
0.720 |
|
Due to the large number of outages experienced
by the station due to transmission line trippings etc.,
the Petitioner has not been able to achieve the norm of 2
ml/kWh fixed by the Honourable Commission for specific oil
consumption. The Petitioner observed a specific oil
consumption of 2.78 ml/kWh during FY 2008-09 The following
Table 7 below provides the trend in specific oil
consumption over the last 7 years.
Table 13: Specific Oil Consumption
|
Year |
Specific Oil
Consumption
(ml/kWh) |
|
2004-05 |
2.33 |
|
2005-06 |
3.39 |
|
2006-07 |
2.31 |
|
2007-08 |
1.95 |
|
2008-09 |
2.78 |
|
Petitioner is planning to reduce its oil consumption and
improve the specific oil consumption figure. Petitioner
projects a specific oil consumption of 2.5 ml/kWh
Table 14: Projected Specific Oil Consumption for FY’10
|
Year |
Specific oil consumption (ml/kWh) |
|
2009-10 |
2.50 |
|
The Petitioner projects the following for the
FY 2008-09:
Table 15: Projected Generation Parameters for FY’07
|
Year |
Generation (MU) |
PLF
(%) |
Auxiliary Consumption (%) |
Heat
Rate (kCal/kWh) |
Specific Coal Consumption (kg/kWh) |
Specific Oil Consumption (ml/kWh) |
|
2000-10 |
2500 |
67.68% |
9 |
3100 |
0.720 |
2.50 |
|
|